ClubEnsayos.com - Ensayos de Calidad, Tareas y Monografias
Buscar

Spring Clamp RTB Cage Clamp RTB


Enviado por   •  21 de Marzo de 2014  •  11.206 Palabras (45 Páginas)  •  311 Visitas

Página 1 de 45

Spring Clamp RTB Cage Clamp RTB

20860-M 20859-M

1. Strip 7/16 inch (11mm) maximum

length of wire.

2. Insert the screwdriver into the

inner hole of the RTB.

3. Insert the wire into the

open terminal and

remove the screwdriver.

1. Strip 3/8 inch (9.5mm) maximum

length of wire.

2. Insert the wire into the open terminal.

3. Turn the screw clockwise to close the

terminal on the wire.

10 ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module

Publication 1756-IN011B-EN-P - February 2003

Wire the Module

You can only connect wiring to your module through an RTB or IFM.

The example below shows how to wire the module.

After completing field-side wiring, secure the wires in the strain relief

area with a cable-tie.

30240-M

2 1

4 3

6 5

8 7

10 9

12 11

14 13

16 15

18 17

20 19

22 21

24 23

26 25

28 27

30 29

32 31

34 33

36 35

Non-isolated

wiring

Isolated wiring

1. All terminals with the same name are connected together on the module. For

example, L1 can be connected to either terminal marked L1-15.

2. When daisy chaining the second L1-15 terminal to other RTBs, always connect the

daisy chain to the terminal directly connected to the supply wire, as shown in the

example above. Do not connect more than 2 wires to any single terminal.

3. If separate power sources are used, do not exceed the specified isolation voltage.

Daisy chain

to other RTBs

1756-OW16I

L1-0

L1-1

L1-2

L1-3

L1-8

L1-4

L1-5

L1-6

L1-7

L1-9

L1-10

L1-11

L1-12

L1-13

L1-14

L1-15

Not used

OUT-0

OUT-1 N.O.

OUT-2 N.O.

OUT-3 N.O.

OUT-8 N.O.

OUT-4 N.O.

OUT-5 N.O.

OUT-6 N.O.

OUT-7 N.O.

Not used

OUT-9 N.O.

OUT-10 N.O.

OUT-11 N.O.

OUT-12 N.O.

OUT-13 N.O.

OUT-14 N.O.

OUT-15 N.O

L1 Not used

Jumper bar

(Cut to length)

DC-4 (-)

L2

L1-15

L2-0

DC-4 (+)

L1-0

L1-2 L2-2

NOTES:

ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module 11

Publication 1756-IN011B-EN-P - February 2003

Assemble the Removable Terminal Block and the Housing

Install the Removable Terminal Block onto the Module

Before installing the RTB, make certain:

 field-side wiring of the RTB has been completed.

 the RTB housing is snapped in place on the RTB.

 the RTB housing is closed.

 the locking tab at the top of the module is unlocked.

!

WARNING When you connect or disconnect the Removable Terminal Block

(RTB) with field side power applied, an electrical arc can occur.

This could cause an explosion in hazardous location

installations. Be sure that power is removed or the area is

nonhazardous before proceeding.

20858–M

Groove

Groove

Side edge of the RTB

Side edge of the RTB

Strain relief area

1. Align the grooves at the bottom of the housing with the side edges of the RTB.

2. Slide the RTB into the housing until it snaps into place.

20853–M 20854–M

Module

guide

RTB guides

Locking tab

1. Align the side and top, bottom guides. 2. Press quickly and evenly to seat the RTB

until the latches snap into place.

3. To lock the RTB on the module,

slide the locking tab down.

12 ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module

Publication 1756-IN011B-EN-P - February 2003

Check the Indicators

The indicators show individual I/O status (yellow) for each point and

a bi-colored LED for module "OK" (red/green).

During power up, an indicator test is done and the following occurs:

 "OK" indicator turns red for 1 second and then turns to

flashing green if it has passed the self-test.

 I/O status indicators turn ON for a maximum of 2 seconds and

then turn OFF.

This completes installation of the module. Use the following

information to remove the module, if necessary.

Indicator: Displaying: Means: Take this action:

OK Steady green

light

The outputs are actively being

controlled by a system

processor.

None

OK Flashing

green light

The module has passed

internal diagnostics but is not

actively controlled.

Configure the module.

OK Flashing red

light

Previously established

communication has timed out.

Check controller and chassis

communication.

OK Steady red

light

An unrecoverable error has

occurred on the module.

Replace the module.

I/O State Yellow The output is active. None

40464

ST 0 1 2 3 4 5 6 7

ST 8 9 10 11 12 13 14 15

O

K

RELAY OUTPUT

ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module 13

Publication 1756-IN011B-EN-P - February 2003

Remove the Removable Terminal Block from the Module

If you need to remove the module, you must remove the RTB first.

Before removing the module, you must remove the RTB.

Remove the Module

!

WARNING When you insert or remove the module while backplane

power is on, an electrical arc can occur. This could cause

an explosion in hazardous location installations. Be sure

that power is removed or the area is nonhazardous

before proceeding.

20855–M

2. Open the RTB door and pull

the RTB off the module.

1. Unlock the locking tab at

the top of the module.

42517

1. Push in top and bottom locking tabs. 2. Pull module out of the chassis.

20856–M 20857–M

14 ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module

Publication 1756-IN011B-EN-P - February 2003

1756-OW16I Specifications

Number of Outputs 16 N.O. (Contacts individually isolated)

Module Location 1756 ControlLogix Chassis

Backplane Current 150mA @ 5.1V dc & 150mA @ 24V dc

(4.4W

...

Descargar como (para miembros actualizados) txt (93 Kb)
Leer 44 páginas más »
Disponible sólo en Clubensayos.com