Spring Clamp RTB Cage Clamp RTB
Enviado por marisela2014 • 21 de Marzo de 2014 • 11.206 Palabras (45 Páginas) • 304 Visitas
Spring Clamp RTB Cage Clamp RTB
20860-M 20859-M
1. Strip 7/16 inch (11mm) maximum
length of wire.
2. Insert the screwdriver into the
inner hole of the RTB.
3. Insert the wire into the
open terminal and
remove the screwdriver.
1. Strip 3/8 inch (9.5mm) maximum
length of wire.
2. Insert the wire into the open terminal.
3. Turn the screw clockwise to close the
terminal on the wire.
10 ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module
Publication 1756-IN011B-EN-P - February 2003
Wire the Module
You can only connect wiring to your module through an RTB or IFM.
The example below shows how to wire the module.
After completing field-side wiring, secure the wires in the strain relief
area with a cable-tie.
30240-M
2 1
4 3
6 5
8 7
10 9
12 11
14 13
16 15
18 17
20 19
22 21
24 23
26 25
28 27
30 29
32 31
34 33
36 35
Non-isolated
wiring
Isolated wiring
1. All terminals with the same name are connected together on the module. For
example, L1 can be connected to either terminal marked L1-15.
2. When daisy chaining the second L1-15 terminal to other RTBs, always connect the
daisy chain to the terminal directly connected to the supply wire, as shown in the
example above. Do not connect more than 2 wires to any single terminal.
3. If separate power sources are used, do not exceed the specified isolation voltage.
Daisy chain
to other RTBs
1756-OW16I
L1-0
L1-1
L1-2
L1-3
L1-8
L1-4
L1-5
L1-6
L1-7
L1-9
L1-10
L1-11
L1-12
L1-13
L1-14
L1-15
Not used
OUT-0
OUT-1 N.O.
OUT-2 N.O.
OUT-3 N.O.
OUT-8 N.O.
OUT-4 N.O.
OUT-5 N.O.
OUT-6 N.O.
OUT-7 N.O.
Not used
OUT-9 N.O.
OUT-10 N.O.
OUT-11 N.O.
OUT-12 N.O.
OUT-13 N.O.
OUT-14 N.O.
OUT-15 N.O
L1 Not used
Jumper bar
(Cut to length)
DC-4 (-)
L2
L1-15
L2-0
DC-4 (+)
L1-0
L1-2 L2-2
NOTES:
ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module 11
Publication 1756-IN011B-EN-P - February 2003
Assemble the Removable Terminal Block and the Housing
Install the Removable Terminal Block onto the Module
Before installing the RTB, make certain:
field-side wiring of the RTB has been completed.
the RTB housing is snapped in place on the RTB.
the RTB housing is closed.
the locking tab at the top of the module is unlocked.
!
WARNING When you connect or disconnect the Removable Terminal Block
(RTB) with field side power applied, an electrical arc can occur.
This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
20858–M
Groove
Groove
Side edge of the RTB
Side edge of the RTB
Strain relief area
1. Align the grooves at the bottom of the housing with the side edges of the RTB.
2. Slide the RTB into the housing until it snaps into place.
20853–M 20854–M
Module
guide
RTB guides
Locking tab
1. Align the side and top, bottom guides. 2. Press quickly and evenly to seat the RTB
until the latches snap into place.
3. To lock the RTB on the module,
slide the locking tab down.
12 ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module
Publication 1756-IN011B-EN-P - February 2003
Check the Indicators
The indicators show individual I/O status (yellow) for each point and
a bi-colored LED for module "OK" (red/green).
During power up, an indicator test is done and the following occurs:
"OK" indicator turns red for 1 second and then turns to
flashing green if it has passed the self-test.
I/O status indicators turn ON for a maximum of 2 seconds and
then turn OFF.
This completes installation of the module. Use the following
information to remove the module, if necessary.
Indicator: Displaying: Means: Take this action:
OK Steady green
light
The outputs are actively being
controlled by a system
processor.
None
OK Flashing
green light
The module has passed
internal diagnostics but is not
actively controlled.
Configure the module.
OK Flashing red
light
Previously established
communication has timed out.
Check controller and chassis
communication.
OK Steady red
light
An unrecoverable error has
occurred on the module.
Replace the module.
I/O State Yellow The output is active. None
40464
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O
K
RELAY OUTPUT
ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module 13
Publication 1756-IN011B-EN-P - February 2003
Remove the Removable Terminal Block from the Module
If you need to remove the module, you must remove the RTB first.
Before removing the module, you must remove the RTB.
Remove the Module
!
WARNING When you insert or remove the module while backplane
power is on, an electrical arc can occur. This could cause
an explosion in hazardous location installations. Be sure
that power is removed or the area is nonhazardous
before proceeding.
20855–M
2. Open the RTB door and pull
the RTB off the module.
1. Unlock the locking tab at
the top of the module.
42517
1. Push in top and bottom locking tabs. 2. Pull module out of the chassis.
20856–M 20857–M
14 ControlLogix™ AC (10-265V) DC (5-150V) Isolated Contact Module
Publication 1756-IN011B-EN-P - February 2003
1756-OW16I Specifications
Number of Outputs 16 N.O. (Contacts individually isolated)
Module Location 1756 ControlLogix Chassis
Backplane Current 150mA @ 5.1V dc & 150mA @ 24V dc
(4.4W
...